ING Bank's main data center in Bucharest, Romania, was severely damaged over the weekend during a fire extinguishing test. In what is a very rare but known phenomenon, it was the loud sound of inert gas being released that destroyed dozens of hard drives. The site is currently offline and the bank relies solely on its backup data center, located within a couple of miles' proximity.

"The drill went as designed, but we had collateral damage", ING's spokeswoman in Romania told me, confirming the inert gas issue. Local clients were unable to use debit cards and to perform online banking operations on Saturday between 1PM and 11PM because of the test. "Our team is investigating the incident," she said.

The purpose of the drill was to see how the data center's fire suppression system worked. Data centers typically rely on inert gas to protect the equipment in the event of a fire, as the substance does not chemically damage electronics, and the gas only slightly decreases the temperature within the data center.


Original Submission

 
This discussion has been archived. No new comments can be posted.
Display Options Threshold/Breakthrough Mark All as Read Mark All as Unread
The Fine Print: The following comments are owned by whoever posted them. We are not responsible for them in any way.
  • (Score: 3, Informative) by Webweasel on Monday September 12 2016, @05:29PM

    by Webweasel (567) on Monday September 12 2016, @05:29PM (#400827) Homepage Journal

    Your a bit out of date:

    The production of Halon 1301 was banned in 1993, a direct result of its negative effects on the ozone layer.

    https://nationalfireinc.com/suppression-systems/inergen-ig-541.html [nationalfireinc.com]

    We use IG-541 Inergen in our data centers, and have had an accidental release.

    No residue on anything the only problem was it cut the power. Servers were more or less fine, nothing major.

    This is UK however, no idea how things are in the US. I'd guess most systems have been replaced now and would be surprised to see halon anywhere.

    --
    Priyom.org Number stations, Russian Military radio. "You are a bad, bad man. Do you have any other virtues?"-Runaway1956
    Starting Score:    1  point
    Moderation   +1  
       Informative=1, Total=1
    Extra 'Informative' Modifier   0  
    Karma-Bonus Modifier   +1  

    Total Score:   3  
  • (Score: 3, Informative) by sjames on Monday September 12 2016, @09:57PM

    by sjames (2882) on Monday September 12 2016, @09:57PM (#400962) Journal

    It's production was banned, but many systems installed before that still have it. For years after, there was a grey market for halon in tanks removed from decommissioned or updated data centers.