https://motherboard.vice.com/read/a-loud-sound-just-shut-down-a-banks-data-center-for-10-hours

ING Bank's main data center in Bucharest, Romania, was severely damaged over the weekend during a fire extinguishing test. In what is a very rare but known phenomenon, it was the loud sound of inert gas being released that destroyed dozens of hard drives. The site is currently offline and the bank relies solely on its backup data center, located within a couple of miles' proximity.

"The drill went as designed, but we had collateral damage", ING's spokeswoman in Romania told me, confirming the inert gas issue. Local clients were unable to use debit cards and to perform online banking operations on Saturday between 1PM and 11PM because of the test. "Our team is investigating the incident," she said.

The purpose of the drill was to see how the data center's fire suppression system worked. Data centers typically rely on inert gas to protect the equipment in the event of a fire, as the substance does not chemically damage electronics, and the gas only slightly decreases the temperature within the data center.


Original Submission

 
This discussion has been archived. No new comments can be posted.
Display Options Threshold/Breakthrough Mark All as Read Mark All as Unread
The Fine Print: The following comments are owned by whoever posted them. We are not responsible for them in any way.
  • (Score: 4, Informative) by tangomargarine on Monday September 12 2016, @09:11PM

    by tangomargarine (667) on Monday September 12 2016, @09:11PM (#400930)

    For example, Halon 1301 total flooding systems are typically used at concentrations no higher than 7% by volume in air, and can suppress many fires at 2.9% v/v. By contrast, carbon dioxide fire suppression flood systems operate from 34% concentration by volume (surface-only combustion of liquid fuels) up to 75% (dust traps). Carbon dioxide can cause severe distress at concentrations of 3–6%, and has caused death by respiratory paralysis in a few minutes at 10% concentration. Halon 1301 causes only slight giddiness at its effective concentration of 5%, and even at 15% those exposed remain conscious but impaired and suffer no long-term effects. (Experimental animals have also been exposed to 2% concentrations of Halon 1301 for 30 hours per week for 4 months, with no discernible health effects.) Halon 1211 also has low toxicity, although it is more toxic than Halon 1301, and thus considered unsuitable for flooding systems.

    However, Halon 1301 fire suppression is not completely non-toxic; very high temperature flame, or contact with red-hot metal, can cause decomposition of Halon 1301 to toxic byproducts.

    https://en.wikipedia.org/wiki/Halomethane#Fire_extinguishing [wikipedia.org]

    --
    "Is that really true?" "I just spent the last hour telling you to think for yourself! Didn't you hear anything I said?"