First, I debated whether to put this on stack exchange or here, but it seems like it is a tech question that suits this site fine.

Background
I have a room with a 115 V, 6000 BTU window AC unit plugged into one outlet. Then a bunch of electronics (~800 W measured) plugged into a 1500 VA, 900 W UPS plugged in to a second outlet across the room. Finally, I have two 50 W strands of Christmas lights in series (100 W total) I tried to plug into various outlets around the room.

Problem
The first problem is that whenever the room gets too hot, the compressor for the AC unit turns on and the Christmas lights will all flicker. This is not just an annoyance, because the first strand of lights I had in the room actually got burned out one by one, starting at the light closest to the wall outlet.

So I got another strand and was surprised to see the flickering happens even if they are plugged into the UPS (which does have an internal automatic voltage regulator). This made me concerned for the electronics plugged into the UPS, which includes a PC and monitors. However, I do not notice any flicker on the monitor when the compressor turns on. On the other hand, I have been getting some strange pc crashes lately (which would make some sense because only recently did it cool enough for the AC to not be running constantly) that may be related. This could also be due to installing a second gpu recently, etc though.

Questions
I have two main questions:

1) What is the best way to stop the flickering?
2) If the lights are flickering even when plugged into the UPS, should I also be concerned about the other electronics that are obviously also experiencing a momentary power reduction?

Some secondary questions:

3) Does it make sense to put another AVR between the UPS and the wall, eg something like this?

4) Is there something I can put between the AC unit and the wall to help?

5) This is a rental so I would prefer not to do any maintenance on the AC unit, but is this an issue you would report to the landlord?

Any ideas?


Original Submission

 
This discussion has been archived. No new comments can be posted.
Display Options Threshold/Breakthrough Mark All as Read Mark All as Unread
The Fine Print: The following comments are owned by whoever posted them. We are not responsible for them in any way.
  • (Score: 1) by NPC-131072 on Sunday November 10 2019, @11:10PM (15 children)

    by NPC-131072 (7144) on Sunday November 10 2019, @11:10PM (#918723) Journal

    What exact measurements do you think would help?

    Watts to confirm problems are caused when the AC switches on.

    This is a rental so I would prefer not to do any maintenance on the AC unit, but is this an issue you would report to the landlord?

    Yes, confirm it's a problem and then get the AC unit and board checked over by an electrician via your landlord.

  • (Score: 0) by Anonymous Coward on Sunday November 10 2019, @11:15PM (14 children)

    by Anonymous Coward on Sunday November 10 2019, @11:15PM (#918725)

    Watts to confirm problems are caused when the AC switches on.

    You mean put the KIllawatt between the AC and the outlet? I've done this but not noticed anything crazy. Possibly because it reports only the average of the last x seconds (where I am not sure how long x refers to). The flickering lasts for ~1/10th of a second.

    • (Score: 1) by NPC-131072 on Monday November 11 2019, @12:17AM (11 children)

      by NPC-131072 (7144) on Monday November 11 2019, @12:17AM (#918753) Journal

      If it's happening when the AC is switching, there's an abnormal power draw. You could check with a decent (safe) multi-meter if you have one?

      Fixed something like this last month on an air compressor, contactor was sticking and needed cleaning and re-greasing but the compressor was also on an old wire fuse at the board and the bakelite holder fell apart when I pulled it. Shot foam into cable holes at the board and used insulation tape around the fuse holder. My fren is now saving for a rewire and new board with RCD's because the arcing at the board had scorched the insulation on one phase of 2 adjacent circuits. Also found a single phase run in metal conduit where some psychomonkey left a live protruding from a screw terminal, replaced that mess with wago connectors housed in a junction box.

      Half the people here could help you fix but on a rental with potential fire / electrocution risk, just get your landlord involved.

      • (Score: 4, Informative) by Runaway1956 on Monday November 11 2019, @01:34AM (10 children)

        by Runaway1956 (2926) Subscriber Badge on Monday November 11 2019, @01:34AM (#918785) Journal

        We don't grease contactors. Grease attracts dust and dirt, making the contactor stick worse. Be aware that the contactor points generate the dust that you find in there. Most greases are also flammable, which will start a fire. Unless you meant dielectric grease? Contactors should be bare-assed copper-to-copper contact. Even if I were to read a maintenance manual on an exotic piece of equipment that specified lubricating the contacts, I would be reluctant to do so.

        If contactors are worn to the point that they need to be maintenanced, you should just replace them. Cleaning and filing them means that you will return in the not-distant future to replace them anyway.

        • (Score: 2) by RS3 on Monday November 11 2019, @03:14AM (5 children)

          by RS3 (6367) on Monday November 11 2019, @03:14AM (#918808)

          Oh gosh, agreed- NEVER grease contacts! That said, I bet someone has some kind of compound for contacts, but normal contact arcing would turn anything into quarks, muons, and neutrinos.

          You might argue in favor of using an anti-corrosion paste on the wires in the terminals / lugs, but never on the contacts.

          You shouldn't need lube on the moving armature, but you could use a light silicone grease or oil, but again, I can't imagine where you'd need it- maybe a moisture compromised location? It might get on the contacts eventually, so either way you'd be replacing the thing.
           

          • (Score: 2, Informative) by NPC-131072 on Monday November 11 2019, @03:28AM (4 children)

            by NPC-131072 (7144) on Monday November 11 2019, @03:28AM (#918816) Journal

            Oh gosh, agreed- NEVER grease contacts! That said, I bet someone has some kind of compound for contacts, but normal contact arcing would turn anything into quarks, muons, and neutrinos.

            Petroleum jelly melts off well before it catches fire. Read any manufacturer advice on isolator switches and it'll state PJ is preventative against arcing since it is non-conductive and gets smudged out of the way at the mechanical point of direct electrical contact.

            • (Score: 0) by Anonymous Coward on Monday November 11 2019, @03:50AM

              by Anonymous Coward on Monday November 11 2019, @03:50AM (#918821)
            • (Score: 2) by RS3 on Monday November 11 2019, @01:41PM

              by RS3 (6367) on Monday November 11 2019, @01:41PM (#918918)

              Thanks, that's very interesting. I tend to avoid risk, so I'd rather not put anything on the contacts which might leave a residue. But if it's helpful, I'll try it. But I'm curious- if it melts off, how is it helpful after the first contact?

            • (Score: 1) by Sally_G on Tuesday November 12 2019, @07:53AM (1 child)

              by Sally_G (8170) on Tuesday November 12 2019, @07:53AM (#919278)

              Read any manufacturer advice on isolator switches and it'll state PJ is preventative against arcing since it is non-conductive and gets smudged out of the way at the mechanical point of direct electrical contact.

                Many of us prefer to read the NEC.

              https://www.browntechnical.org/content/PDF/nec%202014.pdf [browntechnical.org]
              https://www.nfpa.org/Assets/files/AboutTheCodes/70/70-A2013-ROPDraft.pdf [nfpa.org]
              http://www.eng.usf.edu/~fehr/files/2008NEC.pdf [usf.edu]

                One day, I'll locate a current, online, searchable, version of the NFPA 70. Suffice to say that no searches yet have mentioned oiling, greasing, or otherwise lubricating an electrical contactor. Don't take that as an authoritative "NO" yet. The advice already given, to never lubricate electrical contact surfaces is sound advice. Petroleum jelly will supply fuel for a fire, and should not be found inside of an electrical cabinet.

              • (Score: 1) by Sally_G on Tuesday November 12 2019, @09:05AM

                by Sally_G (8170) on Tuesday November 12 2019, @09:05AM (#919293)

                310-9. Corrosive Conditions.
                Conductors exposed to oils,
                greases, vapors, gases, fumes, liquids, or other substances
                having a deleterious effect on the conductor or insulation
                shall be of a type suitable for the application.

        • (Score: 2, Interesting) by NPC-131072 on Monday November 11 2019, @03:18AM

          by NPC-131072 (7144) on Monday November 11 2019, @03:18AM (#918811) Journal

          Cleaned the mechanism and greased electrical contacts using petroleum jelly to prevent arcing. Tested out of circuit using a bench supply and variac - problem was a buildup of crud (oxidization and contaminants) slowing the mechanism from engaging. The rubber seal on the control cabinet had perished and the compressor was in a small room by a grinding area. Didn't trace but basically the contactor was coming from one phase off the control to engage the motor on a big old hydro-vane supplying tool-holders for a bunch of CNC mills at ~100 psi each. Clearly while I wasn't the first in the control cabinet I should be the last, a previous visitor had bypassed a fuse. The thing is a beast and a beat-up, resprayed and franken-fucked pressure vessel like that is a disaster waiting to happen. Told the guy to budget for a modern screw compressor when he's had his electrics redone.

          So I'm confident the contactor will hold until the compressor can be replaced but an electrician hoping to bring the shitshow of his wiring upto code... I made it safe but didn't have the heart to tell him that his existing wiring and '50s bakelite wire fuse board will need replacing along with GFCI breakers. 3x 3-phase circuits plus the single phases for his workshop and probably(?) the sub-main feeding his house :-o

          Shit like this is why I concentrate on my social justice activism!

        • (Score: 0) by Anonymous Coward on Monday November 11 2019, @05:04AM (2 children)

          by Anonymous Coward on Monday November 11 2019, @05:04AM (#918829)

          We don't grease contactors.

          Well, sometimes one has to [wikipedia.org]

          • (Score: 2) by Runaway1956 on Monday November 11 2019, @08:02AM (1 child)

            by Runaway1956 (2926) Subscriber Badge on Monday November 11 2019, @08:02AM (#918856) Journal

            There's no grease in there, now is there? If/when a fumble-fingered tech gets his fingers inside of there, the contactor is no longer good for anything other than recycling.

            • (Score: 2) by RS3 on Monday November 11 2019, @01:46PM

              by RS3 (6367) on Monday November 11 2019, @01:46PM (#918921)

              > There's no grease in there, now is there?

              That, and the wiki doesn't mention it, but I suspect it's under pressure- certainly could build up pressure. And it's a sealed system. The point is, there's no air around the contacts for oxidation / burning to occur.

    • (Score: 1) by paul_engr on Monday November 11 2019, @07:51PM (1 child)

      by paul_engr (8666) on Monday November 11 2019, @07:51PM (#919038)

      The kill-a-watt is probably a few orders of magnitude too slow to measure the dip you are experiencing on line voltage.

      Inrush on a motor load will be 6x operating current, but for a few microseconds(? Not sure, don't quote time scale). You will dip the line voltage enough that your lights will see a corresponding rise in current and net effect will blow first one in the line.

      What kind of lights are they? Regular series incandescent?

      • (Score: 0) by Anonymous Coward on Tuesday November 12 2019, @05:41AM

        by Anonymous Coward on Tuesday November 12 2019, @05:41AM (#919258)

        These are the lights: https://www.amazon.com/gp/product/B0773L1THZ/ [amazon.com]

        But yea, I think that the killawatt is too slow to observe the extent of the surge.