First, I debated whether to put this on stack exchange or here, but it seems like it is a tech question that suits this site fine.

Background
I have a room with a 115 V, 6000 BTU window AC unit plugged into one outlet. Then a bunch of electronics (~800 W measured) plugged into a 1500 VA, 900 W UPS plugged in to a second outlet across the room. Finally, I have two 50 W strands of Christmas lights in series (100 W total) I tried to plug into various outlets around the room.

Problem
The first problem is that whenever the room gets too hot, the compressor for the AC unit turns on and the Christmas lights will all flicker. This is not just an annoyance, because the first strand of lights I had in the room actually got burned out one by one, starting at the light closest to the wall outlet.

So I got another strand and was surprised to see the flickering happens even if they are plugged into the UPS (which does have an internal automatic voltage regulator). This made me concerned for the electronics plugged into the UPS, which includes a PC and monitors. However, I do not notice any flicker on the monitor when the compressor turns on. On the other hand, I have been getting some strange pc crashes lately (which would make some sense because only recently did it cool enough for the AC to not be running constantly) that may be related. This could also be due to installing a second gpu recently, etc though.

Questions
I have two main questions:

1) What is the best way to stop the flickering?
2) If the lights are flickering even when plugged into the UPS, should I also be concerned about the other electronics that are obviously also experiencing a momentary power reduction?

Some secondary questions:

3) Does it make sense to put another AVR between the UPS and the wall, eg something like this?

4) Is there something I can put between the AC unit and the wall to help?

5) This is a rental so I would prefer not to do any maintenance on the AC unit, but is this an issue you would report to the landlord?

Any ideas?


Original Submission

 
This discussion has been archived. No new comments can be posted.
Display Options Threshold/Breakthrough Mark All as Read Mark All as Unread
The Fine Print: The following comments are owned by whoever posted them. We are not responsible for them in any way.
  • (Score: 0) by Anonymous Coward on Monday November 11 2019, @06:40AM

    by Anonymous Coward on Monday November 11 2019, @06:40AM (#918841)

    1) Place AC on separate, dedicated, circuit from the breaker box. Note the word "dedicated", that word is very important and must not be overlooked.

    Did problem go away -- if yes then good.

    If no -- then that means you've exhausted what you can do and you are going to have to contact the power company about the feed lines to your home. The startup draw for a 6k btuh AC, on a dedicated circuit from the breaker box, should not cause noticeable voltage sag to the rest of the house.